Nec 210 8 gfci protection for garages and accessory buildings gfci protection is required for all 15a and 20a 125v receptacles in garages and in grade level portions of unfinished or finished accessory buildings used for storage or work areas of a dwelling unit.
Garage door opener receptacle gfci.
But there was an exception for receptacles that are not readily accessible which is defined as above 6 8 above floor such as a ceiling garage door opener receptacle.
I think it was either 2005 or 2008 nec that they removed all the exceptions for receptacles for dedicated appliances.
But it wasn t always this way.
It used to be that if the outlet wasn t readily accessible then it didn t need to be gfci compliant.
I know in state of wisconsin do not have any extemps on this one beside the frezzer most inspectors got smart with this.
1978 nec garage receptacles first required to be gfci protected.
Remember it isn t the garage door opener or the sump pump that requires gfci protection it is the fact there is a 15 20 amp 120 volt receptacle in a place mentioned in 210 8.
In alberta it has been interpreted that each garage door needs a receptacle and it needs to be placed within 1 m of the expected location of the opener.
Yes even though it is not readily accessible a garage door opener outlet must be gfci protected.
In the past the nec had exceptions for certain receptacles and outlets.
I found a garage door operator plugged into a gfci protected outlet yesterday on new construction.
Receptacle serving a garage door opener is exempted as is a single receptacle for a sump pump when a gfci protected outle t is within 6 feet of the pump.
The gfci circuit breaker located in the panelboard is considered to be readily accessible as a normal installa tion while the gfci receptacle may involve some design location decisions i e.
Afci provisions are added to match those in the 2017 edition of the nec except that an exception is added for branch circuits supplying receptacles which only serve the kitchen counter space.
He said he s only had 1 homeowner in the development call so far because they can t get in their garage since.
More about garage electrical wiring for outlets and lighting.
However since the 2008 edition of the nec that exception went away.
Up until the 2008 edition of the nec national electrical code there were two exceptions allowed for the gfci requirement at garage receptacles.
The reset was inside the garage.
26 714 c one receptacle shall be provided in a garage for each cord connected overhead garage door opener and shall be located within 1 m of the overhead door opener.
Yes all 125 volt single phase 15 or 20 amp receptacles in a garage must be gfci protected with only one esoteric exclusion that we will cover later.
Afaik most states will required every thing on 120 volts in the garage have to be gfci unless overridden by local codes.